Range Pt100 / Pt
1000
-50...70 °C
Pt100 /
Pt1000
-50...400 °C
Ni1000
-50...150 °C
Digital value
Decimal Hex.
Normal
range
:
:
70.0 °C
:
0.1 °C
400.0 °C
:
:
:
0.1 °C
:
150.0 °C
:
:
0.1 °C
4000
1500
700
:
1
0FA0
05DC
02BC
:
0001
0.0 °C 0.0 °C 0.0 °C 0 0000
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-1
:
-500
FFFF
:
FE0C
Measured
value too low
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-50.1 °C
:
-60.0 °C
-501
:
-600
FE0B
:
FDA8
Underflow < -60.0 °C < -60.0 °C < -60.0 °C -32768 8000
Technical data
The system data of AC500 and S500
Ä
Chapter 2.6.1 “System data AC500” on page 971 are
applicable to the standard version.
The system data of AC500-XC
Ä
Chapter 2.7.1 “System data AC500-XC” on page 1023 are
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Process voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24
V (UP) as well as 1.9, 2.9, 3.9 and 4.9
for 0 V (ZP)
Rated value 24 V DC
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
Ca. 2 mA
From UP at normal operation / with outputs 0.15 A + output loads
Inrush current from UP (at power up)
0.050 A
2
s
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US450