EasyManua.ls Logo

ABB AC500 V3 - Functionality

ABB AC500 V3
1029 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functionality
Parameter Value
PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH(W)
PM5032-R-ETH
PM5052-R-ETH
Digital inputs 6 12
Functionality of
digital inputs
(encoder, fast
counter, counter,
interrupt)
6 DI fast input 24 V DC (max. 5
kHz)
usable as
6 DI 24 V DC standard
2 channel 5 kHz encoder with
frequency measurement or
2 channel 5 kHz encoder with
frequency measurement and
with touch/reset using standard
DI or
2 fast counter (5 kHz)
4 DI as interrupt input with
1 dedicated interrupt task and
input information
4 DI fast input 24 V DC (max. 200
kHz)
usable as
4 DI 24 V DC standard or
4 fast counter (100 kHz) or
2 A/B encoder (200 kHz) with
frequency measurement or
2 full A/B encoders 0 and 1 (200
kHz) with frequency measure-
ment and with touch/reset using
standard highspeed (5 kHz) DI
1 full A/B encoder 0 (200 kHz)
with frequency measurement
and optional with touch/reset
using 2 touch/sync inputs with
A/B encoder 0
4 DI fast input 24 V DC (5 kHz)
usable as
4 DI 24 V DC standard or
4 DI as interrupt input with
1 dedicated interrupt task and
input information
4 touch/sync inputs with A/B
encoder 0 or 1
4 standard DI 24 V DC
Digital outputs 4 8 6
Device specifications
Processor modules > AC500-eCo
2022/01/31 3ADR010278, 3, en_US 25

Table of Contents

Other manuals for ABB AC500 V3