Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Technical data of the module
Parameter Value
Process supply voltages UP/UP3
Rated value 24 V DC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Galvanic isolation Ethernet interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.15 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 1.8 and 2.8 for +24 V (UP)
Terminal 3.8 for +24 V (UP3)
Terminals 1.9, 2.9 and 3.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Number of digital inputs 8
Number of digital outputs 8
Number of configurable digital inputs/outputs 8
Input data length 12 bytes
Output data length 20 bytes
Reference potential for all digital inputs and
outputs
Negative pole of the supply voltage, signal
name ZP
Setting of the I/O device identifier With 2 rotary switches at the front side of the
module
Diagnosis
See Diagnosis and Displays
Ä
Chapter
1.7.5.3.8 “Diagnosis” on page 848
Operation and error displays 34 LEDs (totally)
Weight (without terminal unit) Ca. 125 g
Mounting position Horizontal or vertical with derating (output load
reduced to 50 % at 40 °C per group)
Extended ambient temperature (XC version) > 60 °C on request
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Communication interface modules (S500) > PROFINET
2022/01/31 3ADR010278, 3, en_US 855