4 Allocation of signal name
5 Terminal block for input signals (9-pin)
6 Terminal block for input signals (11-pin)
7 2 holes for wall-mounting with screws
8 DIN rail
Intended purpose
The device can be used as a decentralized I/O extension module for S500 communication
iInterface modules (e. g. CI592-CS31, CI501-PNIO, CI541-DP, CI581-CN) or as a centralized
extension module for AC500 CPUs.
The inputs are group-wise galvanically isolated from each other.
The other electronic circuitry of the module is galvanically isolated from the inputs.
The I/O module must not be used as a decentralized I/O module with CI590-
CS31-HA communication interface modules.
Functionality
4 analog TC inputs, individually configurable for
Not used (default)
Voltage -80 mV ... + 80 mV
Thermocouple J-type -210 °C...+1200 °C
Thermocouple K-type -270 °C...+1372 °C
Thermocouple R-type -50 °C...+1768 °C
Thermocouple S-type -50 °C...+1768 °C
Thermocouple T-type -270 °C...+400 °C
Thermocouple E-type -270 °C...+1000 °C
Thermocouple N-type -270 °C...+1300 °C
Parameter Value
Resolution of the analog channels
Temperature 0.1 °C
LED displays 2 LEDs for process voltage and error mes-
sages
Internal supply Via I/O bus
External supply Via the terminals UP (process voltage 24 V
DC) and ZP (0 V DC)
Connections
For a detailed description of the mounting, disassembly and connection of the
module, please refer to the System Assembly chapter
Ä
Chapter 2.5 “AC500-
eCo” on page 925.
Device specifications
I/O modules > Analog I/O modules