Parameter Value
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication inter-
face module
ca. 2 mA
From UP at normal operation / with outputs 0.15 A + output loads
Inrush current from UP (at power up)
0.004 A
2
s
Max. power dissipation within the module 6 W (outputs OFF)
Weight (without terminal unit) Ca. 300 g
Mounting position Horizontal or vertical with derating
(output load reduced to 50 % at 40
°C per group)
Cooling The natural convection cooling
must not be hindered by cable
ducts or other parts in the switch-
gear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
No effects of multiple overloads on isolated multi-channel modules occur, as every channel is
protected individually by an external fuse.
Technical data of the digital inputs
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 4 groups of 2 channels each
Terminals of the channels I0 to I7
Ä
Chapter 1.6.1.2.8.3 “Connections”
on page 340
Galvanic isolation 2500 V AC from the rest of the module (I/O
bus)
Indication of the input signals 1 yellow LED per channel
The LEDs are only operating if the module is
initialized
Monitoring point of input indicator LED is controlled by process CPU
Input type acc. to EN 61131-2 Type 2
Input delay (0->1 or 1->0) Typ. 20 ms
Input signal voltage 230 V AC or 120 V AC
No effects of
multiple over-
loads
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 347