The meaning of the LEDs is described in Displays
Ä
Chapter 1.7.5.2.8.2 “State LEDs”
on page 826.
Connection of resistance thermometers in 2-wire configuration to the analog inputs
When resistance thermometers (Pt100, Pt1000, Ni1000) are used, a constant current must
flow through them to build the necessary voltage drop for the evaluation. For this, the module
CI501-PNIO provides a constant current source which is multiplexed over the max. 4 analog
input channels.
The following figure shows the connection of resistance thermometers in 2-wire configuration to
the analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Device specifications
Communication interface modules (S500) > PROFINET
2022/01/31 3ADR010278, 3, en_US 803