ABB AC500 V3 - 2.6.1.2 Creepage distances and clearances; 2.6.1.3 Insulation test voltages, routine test

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NOTICE!
Improper voltage level or frequency range which cause damage of AC inputs:
AC voltage above 264 V
Frenquency below 47 Hz or above 62.4 Hz
NOTICE!
Improper connection leads cause overtemperature on terminals.
PLC modules may be destroyed by using wrong cable type, wire size and cable
temperature classification.
Parameter Value
Temperature
Operating 0 °C...+60 °C: Horizontal mounting of modules.
0 °C...+40 °C: Vertical mounting of modules.
Output load reduced to 50 % per group.
Storage -40 °C...+70 °C
Transport -40 °C...+70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Ingress protection IP20
2.6.1.2 Creepage distances and clearances
The creepage distances and clearances meet the requirements of the overvoltage category II,
pollution degree 2.
2.6.1.3 Insulation test voltages, routine test
Parameter Value
230 V circuits against other
circuitry
2500 V 1.2/50 µs
120 V circuits against other
circuitry
1500 V 1.2/50 µs
120 V...240 V circuits against
other circuitry
2500 V 1.2/50 µs
24 V circuits (supply, 24 V
inputs/outputs, analog inputs/
outputs), if they are galvani-
cally isolated against other cir-
cuitry
500 V 1.2/50 µs
According to EN
61131-2
System assembly, construction and connection
AC500 (Standard) > System data AC500
2022/01/313ADR010278, 3, en_US972