EasyManua.ls Logo

ABB AC500 V3 - Connection of passive-type analog sensors (Current) to the analog inputs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 79: Connection of active-type sensors (voltage) with no galvanically isolated power supply
to the analog inputs
CAUTION!
Risk of faulty measurements!
The negative pole at the sensors must not have too big a potential difference
with respect to ZP (max. ±1 V within the full signal range).
Make sure that the potential difference never exceeds ±1 V.
The following measuring ranges can be configured
Ä
Chapter 1.6.3.1.1.6 “Parameterization”
on page 565:
Voltage 0 V...10 V 1 channel used
Voltage -10 V...+10 V 1 channel used
For a description of the function of the LEDs, please refer to the Diagnosis and displays /
Displays chapter
Ä
Chapter 1.6.3.1.1.8 “State LEDs” on page 572.
To avoid error messages from unused analog input channels, configure them as "unused".
Connection of passive-type analog sensors (Current) to the analog inputs
The following figure shows the connection of passive-type analog sensors (current) to the
analog input AI0. Proceed with the analog inputs AI1 to AI3 in the same way.
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 559

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals