Parameter Value
Shielded On request
Unshielded On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Technical data of the digital relay outputs
Table 17: PM5012-R-ETH
Parameter Value
Number of channels per module 4 normally-open relay outputs
Distribution of the channels into groups 2 groups for 2 channels
Galvanic isolation Yes, per group
Connection of the channels NO0 to NO1 Terminals 8 to 9
Connection of the channels NO2 to NO3 Terminals 11 to 12
Reference potential R0..1 for the channels NO0
to NO1
Terminal 10
Reference potential R2..3 for the channels NO2
to NO3
Terminal 13
Relay output voltage
Rated value 24 V DC or
100 V AC...240 V AC
50 Hz/60 Hz
Range 5 V DC...30 V DC
or
5 V AC...250 V AC
Indication of the output signals 1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Way of operation Non-latching type
Output delay
0 to 1 Typ. 10 ms
1 to 0 Typ. 10 ms
Rated protection fuse On request
Output current
Rated current per channel (max.) 2.0 A (24 V DC resistance and general use,
100 V AC...240 V AC, resistance, general
use and pilot duty)
Rated current per group (max.) 6 A
Rated current (all channels together, max.) 12 A
Demagnetization when inductive loads are
switched off
External demagnetization measures must be
implemented when switching inductive loads.
Spark suppression with inductive AC loads Must be performed externally according to
driven load specification
Switching frequencies
Device specifications