EasyManua.ls Logo

ABB AC500 V3 - 2.4.6 Decommissioning

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fuse for S of the
melting
integrals in
A²s
I
Logic A
I
UPx A
Recommended fuse
Type Value
F1 CPU logic 1.000 » 0.4 - Quick 10 A
F2 Module Dig-
ital1
0.005 - 8.050 Quick 10 A
F3 Module Dig-
ital2
0.008 - 8.050 Quick 10 A
F4 Module Dig-
ital3
0.007 - 8.050 Quick 10 A
F5 Modules
Analog1 +
Analog2 +
Analog3 +
Analog4
0.130 - 0.820 Quick 10 A
2.4.6 Decommissioning
1. Delete the runtime licenses.
2. Delete certificates available on the CPU.
3. Delete applications.
4. Delete applications from memory card, if available.
5. If available, remove memory card and battery from CPU.
6. Delete all user accounts and user data.
7.
Demount and dispose the hardware modules
Ä
Chapter 2.5.3 “Mounting and demounting”
on page 933
Ä
Chapter 2.6.3 “Mounting and demounting” on page 981
Ä
Chapter
2.4.7 “Recycling” on page 925.
If you can not access the data stored in the CPU, e.g., because the CPU is not functional
any more, then physically destroy the device.
ð
This ensures that the credentials that are stored in the device, can not be misused.
Secure decom-
missioning of a
functional CPU
Secure decom-
missioning of a
not functional
CPU
System assembly, construction and connection
Overall information (valid for complete AC500 product family) > Decommissioning
2022/01/313ADR010278, 3, en_US924