Name Value Internal
value
Internal
value,
type
Default Min. Max. Max.
Substitute
value at
outputs
Bit 7 =
Output 7
Bit 0 =
Output 0
0...255 0...0xff BYTE 0x00 0 255 0x0Y06
Reserve 0...255 0...0xff BYTE 0x00 0 255 0x0Y07
Reserve 0...255 0...0xff BYTE 0x00 0 255 0x0Y08
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len = 10
Ext_User_Prm_Data_Const(0) =
0x04, 0x51, 0x00, 0x06, 0x01, 0x01, 0x00,
0x00, 0x00, 0x00
State LEDs
During the power ON procedure, the module initializes automatically. All LEDs (except the
channel LEDs) are ON during this time.
LED State Color LED = OFF LED = ON LED flashes
Outputs
O0...O7
Digital output Yellow Output =
OFF
Output = ON
2
)
--
UP Process
supply
voltage
24 V DC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
UP3 Process
supply
voltage out-
puts 0...3
24 V DC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
UP4 Process
supply
voltage out-
puts 4...7
24 V DC via
terminal
Green Process
supply
voltage is
missing
Process
supply voltage
OK
--
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US324