Connection of thermocouples
Fig. 49: Connection example
The following measuring ranges can be configured
Ä
Chapter 1.6.2.2.3.6 “Parameterization”
on page 472 :
J type -210 °C...1200 °C Fe-CuNi 1 channel used
K type -270 °C...1372 °C Ni-CrNi 1 channel used
N type -270 °C...1300 °C NiCrSi-NiSi 1 channel used
S type -50 °C...1768 °C Pt10Rh-Pt 1 channel used
T type -270 °C...400 °C Cu-CuNi 1 channel used
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US470