Parameter Value
PM5012-x-ETH PM5032-
x-ETH
PM5052-
x-ETH
PM5072-
T-2ETH
PM5072-T-2ETHW
Temperature
Operating
Horizontal mounting
Standard temperature
range
0 °C...+55 °C 0 °C...+60 °C -
Wide temperature
range
- -20 °C...+70 °C
I/O derating
in range
60 °C…70 °C:
75 %
Vertical mounting (output load reduced to 50 % per group)
Standard temperature
range
0 °C...+40 °C -
Wide temperature
range
- -20 °C...+40 °C
Storage -40 °C...+70 °C
Transport -40 °C...+70 °C
Humidity Max. 95 %, without condensation
Air pressure
Operating > 800 hPa / < 2000 m
Storage > 660 hPa / < 3500 m
Ingress protection PLC System: IP 20 in accordance with IEC 60529
with all modules or option boards plugged in
with all terminal blocks plugged in
with all covers closed
Option boards Temperature range
TA5101-4DI 0 °C... 60 °C
TA5105-4DOT 0 °C... 60 °C
TA5110-2DI2DOT 0 °C... 60 °C
TA530-KNXPB 0 °C... 60 °C
TA5131-RTC 0 °C...+55 °C
TA5141-RS232I 0 °C... 60 °C
TA5142-RS485I 0 °C... 60 °C
TA5142-RS485 0 °C... 60 °C
2.5.1.2 Creepage distances and clearances
The creepage distances and clearances meet the requirements of the overvoltage category II,
pollution degree 2.
System assembly, construction and connection
AC500-eCo > System data AC500-eCo V3
2022/01/313ADR010278, 3, en_US926