EasyManua.ls Logo

ABB AC500 V3 - I;O Configuration; Parameterization

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
The module provides several diagnosis functions
Ä
Chapter 1.6.1.1.1.6 “Diagnosis”
on page 147.
The meaning of the LEDs is described in the section State LEDs
Ä
Chapter 1.6.1.1.1.7 “State
LEDs” on page 147.
I/O Configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
The arrangement of the parameter data is performed with Automation Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Name Value Internal
Value
Internal
Value,
Type
Default Min. Max. EDS Slot
Index
Module ID Internal
6100
1
)
WORD 6100
0x17D4
0 65535 xx01
Ignore
module
No
Yes
0
1
BYTE No
(0x00)
Parameter
length
2
)
Internal 1 - CPU BYTE 0 0 255
xx02
3
)
Remarks:
1
)
With CS31 and addresses smaller than 70, the value is increased by 1
2
)
The module has no additional user-configurable parameters
3
)
Value is hexadecimal: HighByte is slot (xx: 0...7), LowByte is index (1...n)
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
0x03
0x25, 0x17, 0x00;
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US146

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals