There are three important principles to be especially considered:
Keep all connections as short as possible (in particular the grounding con-
ductors)
Use large conductor cross sections (in particular for the grounding conduc-
tors)
Create low-impedance, i.e. good and large-sized contacts (in particular for
the grounding conductors)
Pay attention to the following:
Use vibration-resistant connections
Clean metallic contact areas
Use solid plug and screw-type connections
Use earth cable shields with clips on a well-grounded metallic surface
Do not use aluminium parts
Do not use sheath wires
Do not use toothed lock washers under screw connections
Fig. 173: Assembly: wrong
Fig. 174: Assembly: correct
Make a connection between the DIN rails and PE (Protective Earth). For this, use an grounding
wire with a minimum conductor cross section of 10 mm².
The wire is connected to the DIN rail with an M6 screw.
A large-area contact of the DIN rail with the metallic mounting plate improves the EMC behavior
significantly, as the disturbances can be discharged more effective.
2.4.4.2 Cable routing
Route cables meeting the standards.
Sort the cables into cable groups:
Power current cables
Power supply cables
Signal cables
Data cables
System assembly, construction and connection
Overall information (valid for complete AC500 product family) > EMC-conforming assembly and construction
2022/01/31 3ADR010278, 3, en_US 919