Parameter Value
Channels C0...C7 Terminals 2.0...2.7
Channels C8 C15 Terminals 3.0...3.7
Channels C16...C23 Terminals 4.0...4.7
Indication of the input/output signals 1 yellow LED per channel, the LED is ON when
the input/output signal is high (signal 1)
Monitoring point of input/output indicator LED is part of the input circuitry
Galvanic isolation From the rest of the module
Technical data of the digital inputs/outputs if used as inputs
Parameter Value
Number of channels per module Max. 24 digital inputs
Reference potential for all inputs Terminals 1.9, 2.9, 3.9 and 4.9 (negative pole
of the process supply voltage, signal name
ZP)
Galvanic isolation From the rest of the module
Indication of the input signals 1 yellow LED per channel, the LED is ON
when the input signal is high (signal 1)
Monitoring point of input/output indicator LED is part of the input circuitry
Input type acc. to EN 61131-2 Type 1
Input delay (0->1 or 1->0) Typ. 8 ms, configurable from 0.1 to 32 ms
Input signal voltage 24 V DC
Signal 0 -3 V...+5 V *)
Undefined signal > +5 V...< +15 V
Signal 1 +15 V...+30 V
Ripple with signal 0 Within -3 V...+5 V *)
Ripple with signal 1 Within +15 V...+30 V
Input current per channel
Input voltage +24 V Typ. 5 mA
Input voltage +5 V > 1 mA
Input voltage +15 V > 5 mA
Input voltage +30 V < 8 mA
Max. cable length
Shielded 1000 m
Unshielded 600 m
*) Due to the direct connection to the output, the demagnetizing varistor is also effective at the
input (see figure) above. This is why the difference between UPx and the input signal must not
exceed the clamp voltage of the varistor. The varistor limits the clamp voltage to approx. 36 V.
Consequently, the input voltage must range from -12 V to +30 V when UPx = 24 V and from
-6 V to +30 V when UPx = 30 V.
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US288