Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module slot address: Y = 1...7
No. Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
1 Module
ID
Internal 1500
1
)
Word 1500
0x05dc
0 65535 0x0Y01
2 Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
not for
FBP
3 Param-
eter
length in
bytes
Internal 37 Byte 37-CPU
37-FBP
0 255 0x0Y02
4 Check
supply
Off
On
0
1
Byte On
0x01
0 1 0x0Y03
5 Analog
data
format
Default 0 Byte Default
0x00
0x0Y04
6 Behav-
iour of
outputs
at com-
munica-
tion
errors
Off
Last
value
Substi-
tute
value
0
1+(n*5)
2+(n*5),
n £ 2
Byte Off
0x00
0 2 0x0Y05
7 Channel
configu-
ration
Input
channel
0
See
Ä
Table 111 “Chan
nel configuration
2
)”
on page 538
Byte Default
0x00
0 19 0x0Y06
8 Channel
moni-
toring
Input
channel
0
See
Ä
Table 112 “Chan
nel monitoring
3
)”
on page 539
Byte Default
0x00
0 3 0x0Y07