EasyManua.ls Logo

ABB AC500 V3 - Connection of analog output loads (Voltage, current); Internal data exchange; I;O configuration

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Connection of analog output loads (Voltage, current)
UP
ZP
1.0
O0-
1.1
O1-
1.8
UP
1.9
ZP
PTC
2.0
O0+
2.1
O1+
2.8
UP
2.9
ZP
-10 ... +10 V
0 ... 20 mA
4 ... 20 mA
Fig. 51: Connection example
The following measuring ranges can be configured
Ä
Chapter 1.6.2.2.4.6 “Parameterization”
on page 491:
Voltage -10 V...+10 V Load max. ±10 mA 1 channel used
Current 0 mA...20 mA Load 0 W...500 W 1 channel used
Current 4...20 mA Load 0 W...500 W 1 channel used
Only the channels 0...3 and 8...11 can be configured as current output (0 mA...20 mA or 4
mA...20 mA).
The function of the LEDs is described under Displays.
Unused analog outputs can be left open-circuited.
Internal data exchange
Digital inputs (bytes) 0
Digital outputs (bytes) 0
Counter input data (words) 0
Counter output data (words) 16
I/O configuration
The module does not store configuration data itself. It gets its parameterization data from the
master device of the I/O bus (CPU or communication interface module) during power-up of the
system.
That means replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Device specifications
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US490

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals