EasyManua.ls Logo

ABB AC500 V3 - Unipolar voltage input range, measuring bridge, digital input; Current input ranges

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range -50 ...
+50 mV
-500 ...
+500
mV
-1 ... +1
V
-5 ... +5
V
-10 ...
+10 V
Commo
n Mode
Voltage
Digital value
Decimal Hex.
Meas-
ured
value
too low
-50.0018
:
-58.7945
-500.018
1
:
-587.944
9
-1.00004
:
-1.17589
-5.0002
:
-5.8794
-10.0004
:
-11.7589
-27649
:
-32512
93FF
:
8100
Under-
flow
<
-58.7945
<
-587.944
9
<
-1.17589
<
-5.8794
<
-11.7589
<
-20.0000
-32768 8000
Unipolar voltage input range, measuring bridge, digital input
Range 0 ... +5 V 0 ... +10 V Digital
input
Digital value
Decimal Hex.
Measured
value too
high
5.8794
:
5.0002
11.7589
:
10.0004
32511
:
27649
7EFF
:
6C01
Normal
range
5.0000
:
0.0002
10.0000
:
0.0004
ON
27648
:
1
6C00
:
0001
0.0000 0.0000 OFF 0 0000
Measured
value too
low
-0.0002
:
-0.8794
-0.0004
:
-1.1759
-1
:
-4864
FFFF
:
ED00
Underflow < -0.8794 < -1.1759 -32768 8000
Current input ranges
Range -20 ... +20
mA
0 ... +20 mA 4 ... 20 mA Digital value
Decimal Hex.
Overflow > 23.5178 > 23.5178 > 22.8142 32767 7FFF
Measured
value too
high
23.5178
:
20.0007
23.5178
:
20.0007
22.8142
:
20.0006
32511
:
27649
7EFF
:
6C01
Normal
range
20.0000
:
0.0007
20.0000
:
0.0007
20.0000
:
4.0006
27648
:
1
6C00
:
0001
0.0000 0.0000 4.0000 0 0000
-0.0007
:
-20.0000
-1
:
-27648
FFFF
:
9400
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 479