Table 207: Ordering data
Order No. Type Input Output Overload
capacity
Module
width [mm]
1SVR360563R1001 CP-C.1
24/5.0
110-240 V
AC or
90-300 V DC
24 V DC, 5 A +50 % 40
1SVR360663R1001 CP-C.1
24/10.0
110-240 V
AC or
90-300 V DC
24 V DC, 10
A
+50 % 60
1SVR360763R1001 CP-C.1
24/20.0
110-240 V
AC or
90-300 V DC
24 V DC, 20
A
+30 % 82
2.7 AC500-XC
2.7.1 System data AC500-XC
Assembly, construction and connection of devices of the variant AC500-XC is
identical to AC500 (standard)
Ä
Chapter 2.6 “AC500 (Standard)” on page 971.
The following description provides information on general technical data of
AC500-XC system.
2.7.1.1 Environmental conditions
Table 208: Process and supply voltages
Parameter Value
24 V DC
Voltage 24 V (-15 %, +20 %)
Protection against reverse polarity Yes
120 V AC...240 V AC wide-range supply
Voltage 120...240 V (-15 %, +10 %)
Frequency 50/60 Hz (-6 %, +4 %)
Allowed interruptions of power supply
DC supply Interruption < 10 ms, time between 2 interrup-
tions > 1 s, PS2
NOTICE!
Exceeding the maximum power supply voltage for process or supply voltages
could lead to unrecoverable damage of the system. The system might be
destroyed.
NOTICE!
For the supply of the modules, power supply units according to PELV or SELV
specifications must be used.
System assembly, construction and connection
AC500-XC > System data AC500-XC
2022/01/31 3ADR010278, 3, en_US 1023