If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal value Internal
value, type
Default EDS Slot /
Index
Module ID
1
)
Internal 1815 WORD 1815 0x0Y01
Ignore module Internal Yes
No
BYTE No
Parameter
length
Internal 8 BYTE 8 0xY02
Check supply off 0 BYTE 1 0xY03
on 1
Fast counter
3
)
0
:
10
2
)
0
:
10
BYTE 0 Not for FBP
Behavior out-
puts at comm.
error
5
)
Off Last value
Last value 5 s
Last value 10
s Substitute
value
Substitute
value 5 s
Substitute
value 10 s
0
1 6
11
2
7
12
BYTE Off
0x00
0x0Y07
2
)
Setting Description
On Error LED lights up at errors of all error
classes, Failsafe mode off
Off by E4 Error LED lights up at errors of error
classes E1, E2 and E3, Failsafe mode off
Off by E3 Error LED lights up at errors of error
classes E1 and E2, Failsafe mode off
I/O modules > Digital/Analog I/O modules