If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
Module ID Internal 1205
1
)
Word 1205
0x04B5
0 65535 0x0Y01
Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
not for
FBP
Parameter
length
Internal 4 Byte 4-CPU
4-FBP
0 255 0x0Y02
Check
supply
Off
on
0
1
Byte On
0x01
0 1 0x0Y03
Input
delay
20 ms
100 ms
0
1
Byte 20 ms
0x00
0 1 0x0Y04
Behaviour
of outputs
at com-
munica-
tion errors
Off
Last value
Substitute
value
0
1+(n*5)
2+(n*5),
n £ 2
Byte Off
0x00
0 2 0x0Y05
Substitute
value at
outputs
Bit 3 =
Output 3
Bit 0 =
Output 0
0...15 0...
0x0f
Byte 0
0x00
0 15 0x0Y06
1
) With CS31 and addresses smaller than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Device specifications
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 345