NOTICE!
Risk of influences to the connected sensors!
Some sensors may be influenced by the deactivated module outputs of DC532.
Connect a 470 W / 1 W resistor in series to inputs C24/C25 if using them as fast
counter inputs to avoid any influences.
The module provides several diagnosis functions .
Internal data exchange
Without the fast counter With the fast counter (only
with AC500)
Digital inputs (bytes) 4 6
Digital outputs (bytes) 2 4
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O configuration
The module itself does not store configuration data. It receives its parameterization data from
the master device of the I/O bus (CPU or communication interface module) during power-up of
the system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
If the external power supply voltage via UP/ZP terminals fails, the I/O module
loses its configuration data. The whole station has to be switched off and on
again to re-configure the module.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
I/O modules > Digital I/O modules