Functionality
Parameter Value
LED displays For signal states
Internal power supply Via I/O bus
External power supply Via the terminal L+ (process voltage 24 V DC). The negative
pole is provided by the I/O bus.
Connections
For a detailed description of the mounting, disassembly and connection of the
module, please refer to the System Assembly chapter
Ä
Chapter 2.5 “AC500-
eCo” on page 925.
The connection is carried out by using removable 9-pin and 11-pin terminal blocks. These
terminal blocks differ in their connection system (spring terminals or screw terminals, cable
mounting from the front or from the side). The terminal blocks are not included in the module's
scope of delivery and must be ordered separately.
The following block diagram shows the internal construction of the digital outputs:
NO212
NO111
R0..314
NO313
NO617
NO516
R4..719
NO718
NO010
NO415
L+20
Table 68: Assignment of the terminals:
Terminal Signal Description
10 NO0 Normally-open contact of the output NO0
11 NO1 Normally-open contact of the output NO1
12 NO2 Normally-open contact of the output NO2
13 NO3 Normally-open contact of the output NO3
14 R0..3 Output common for signals NO0 to NO3
15 NO4 Normally-open contact of the output NO4
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 213