ABB AC500 V3 - Functionality; Connections

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Digital configurable input/output unit.
2 sensor supply voltages 24 V DC, 0.5 A, with short-circuit and overload protection
16 digital configurable inputs/outputs 24 V DC (C0 to C15) in 1 group (2.0...2.7 and
4.0...4.7), each of which can be used
as an input,
as a transistor output with short-circuit and overload protection, 0.5 A rated current or
as a re-readable output (combined input/output) with the technical data of the digital
inputs and outputs.
Optional with fast counter
The configuration is performed by software. The modules are supplied with a process supply
voltage of 24 V DC.
All available inputs/outputs are galvanically isolated from all other circuitry of the module. There
is no potential separation between the channels within the same group.
For use in extreme ambient conditions (e.g. wider temperature and humidity range), a special
XC version of the device is available.
Functionality
Parameter Value
Fast counter Integrated, many configurable operating
modes (only with AC500)
LED displays For signal states, errors and supply voltage
Internal power supply Through the I/O bus interface (I/O bus)
External power supply Via the terminals ZP and UP (process voltage
24 V DC)
Required terminal unit
TU515 or TU516
Ä
Chapter 1.5.2 “TU515,
TU516, TU541 and TU542 for I/O modules”
on page 126
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
The device is plugged on a terminal unit
Ä
Chapter 1.5.2 “TU515, TU516, TU541 and TU542
for I/O modules” on page 126. Position the module properly and press until it locks in place. The
terminal unit is either mounted on a DIN rail or to the wall using 2 screws plus the additional
accessory for wall mounting (TA526
Ä
Chapter 1.8.2.6 “TA526 - Wall mounting accessory”
on page 902).
Connections
The connection of the I/O channels is carried out using the 40 terminals of the I/O terminal unit.
I/O modules can be replaced without re-wiring the terminal units.
The terminals 1.8 to 4.8 and 1.9 to 4.9 are electrically interconnected within the I/O terminal unit
and always have the same assignment, irrespective of the inserted module:
Terminals 1.8 to 4.8: process voltage UP = +24 V DC
Terminals 1.9 to 4.9: process voltage ZP = 0 V DC
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US270