EasyManua.ls Logo

ABB AC500 V3 - 1.3.1.1.2 Assortment; 1.3.1.1.3 Connections and interfaces

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1.3.1.1.2 Assortment
Processor
module
Total
max-
imu
m
dow
nloa
dabl
e
appli
catio
n
size
Allocated
global
user
memory
for user
program
code and
data
Cycle
time for
1000
instructio
ns [ns]
Numer
digital
inputs
Number
digital
outputs
Type of
digital
outputs
Config-
urable
digital
inputs/
outputs
Number
of option
board
slots
Max.
number
of I/O
modules
on I/O
bus
PM5012-T-
ETH
1 MB 256 kB Binary: 20
Word: 50
Floating:
600
6 4 Tran-
sistor
- 1 -
PM5012-
R-ETH
1 MB 256 kB 6 4 Relay - 1 -
PM5032-T-
ETH
2 MB 512 kB 12 8 Tran-
sistor
2 2 10 with
max. 128
Bytes
inputs/
128
Bytes
outputs
variables
PM5032-
R-ETH
2 MB 512 kB 12 6 Relay 2 2 10 with
max. 128
Bytes
inputs/
128
Bytes
outputs
variables
PM5052-T-
ETH
4 MB 768 kB 12 8 Tran-
sistor
2 3 10
PM5052-
R-ETH
4 MB 768 kB 12 6 Relay 2 3 10
PM5072-
T-2ETH
8 MB 1 MB 12 8 Tran-
sistor
2 3 10
PM5072-
T-2ETHW
8 MB 1 MB 12 8 Tran-
sistor
2 3 10
1.3.1.1.3 Connections and interfaces
The I/O bus is not available for PM5012-T-ETH and PM5012-R-ETH. I/O
channel extension using option board slot only.
The I/O bus is the I/O data bus for the I/O modules. Through this bus, I/O and diagnosis data
are transferred between the processor module and the I/O modules. Up to 10 I/O modules for
PM5032-x-ETH (but with a limit of 128 Bytes input/ 128 Bytes output variables) and 10 I/O
modules for PM5052-x-ETH and PM5072-T-2ETH can be added.
I/O bus
Device specifications
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US18

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals