EasyManua.ls Logo

ABB AC500 V3 - Technical data of the digital transistor outputs

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter PM5012-T-ETH PM5012-R-ETH PM5032-T-ETH
PM5052-T-ETH
PM5072-
T-2ETH
PM5032-R-
ETH
PM5052-R-
ETH
Fast input
max. 5 kHz
- - DI0 ... DI3 DI0 ... DI3
Fast input,
max. 100 kHz
- - DI6 ... DI7
When using the
A/B encoder on
DI04...DI05 and
the Touch/
Reset inputs on
fast inputs
DI6 ... DI7
When using the
A/B encoder on
DI04...DI05 and
the Touch/
Reset inputs on
fast inputs
Technical data of the digital transistor outputs
Table 15: PM5012-T-ETH
Parameter Value
Number of channels per module 4
Distribution of the channels into groups 1 group of 4 channels
Galvanic isolation Yes, per group
Connection of the channels O0 to O3 Terminals 8 to 11
Common power supply voltage Terminals 12 (+24 V DC, signal name UP)
Reference potential for the channels O0 to O7 Terminal 13 (0 V DC, negative pole of the
process voltage, signal name ZP)
Indication of the output signals 1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Way of operation Non-latching type
Min. output voltage at signal 1 UP - 0.1 V
Output delay (max. at rated load)
0 to 1 On request
1 to 0 On request
Rated protection fuse (per group) On request
Output current
Rated current per channel (max.) 0.5 A at UP 24 V DC (resistance, general
use and pilot duty)
Rated current per group (max.) 2 A
Rated current (all channels together, max.) 2 A
Max. leakage current with signal 0 On request
Demagnetization when inductive loads are
switched off
Must be performed externally according to
driven load specification
Switching Frequencies
With inductive loads On request
Short-circuit-proof / Overload-proof No
Overload message No
Device specifications
Processor modules > AC500-eCo
2022/01/313ADR010278, 3, en_US38

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals