Parameter Value
Output current limitation No
Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Max. cable length *)
Shielded On request
Unshielded On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Table 16: PM5032-T-ETH, PM5072-T-2ETH and PM5072-T-2ETHW
Parameter Value
Number of channels per module 8
Distribution of the channels into groups 1 group of 8 channels
Galvanic isolation Yes, per group
Connection of the channels O0 to O7 Terminals 14 to 21
Common power supply voltage Terminals 24 (+24 V DC, signal name UP)
Reference potential for the channels O0 to O7 Terminal 25 (0 V DC, negative pole of the
process voltage, signal name ZP)
Indication of the output signals 1 yellow LED per channel; the LED is on
when the output signal is high (signal 1)
Way of operation Non-latching type
Min. output voltage at signal 1 UP - 0.1 V
Output delay (max. at rated load)
0 to 1 On request
1 to 0 On request
Rated protection fuse (per group) On request
Output current
Rated current per channel (max.) 0.5 A at UP 24 V DC (resistance, general
use and pilot duty)
Rated current per group (max.) 4 A
Rated current (all channels together, max.) 4 A
Max. leakage current with signal 0 0.5 mA
Demagnetization when inductive loads are
switched off
Must be performed externally according to
driven load specification
Switching Frequencies
With inductive loads On request
Short-circuit-proof / Overload-proof No
Overload message No
Output current limitation No
Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Max. cable length *)
Processor modules > AC500-eCo
2022/01/31 3ADR010278, 3, en_US 39