Range Typ J
-210 ...
+1200 °C
Typ K
-270 ...
+1372 °C
Typ N
-270 ...
+1300 °C
Typ S
-50 ...
+1768 °C
Typ T
-270 ...
+400 °C
Digital value
Decimal Hex.
0.1 °C 0.1 °C 0.1 °C 0.1 °C 0.1 °C 1 1
0.0 °C 0.0 °C 0.0 °C 0.0 °C 0 0000
-0.1 °C -0.1 °C -0.1 °C -0.1 °C -0.1 °C -1 FFFF
: : : : : : :
: : : -50.0 °C : -500 FE0C
-210.0 °C : : : : -2100 F7CC
-270.0 °C -270.0 °C -270.0 °C -2700 F574
Under-
flow
< -210.0
°C
< -270.0
°C
< -270.0
°C
< -50.0
°C
< -270.0
°C
-32768 8000
Temperature-internal reference point ranges
Range Value Digital value
Decimal Hex.
Overflow > +85 °C 32767 7FFF
Normal range +85 °C 850 0352
0 °C 0 0000
-40 °C -400 FE70
Underflow < -40 °C -32768 8000
Technical data
The system data of AC500 and S500
Ä
Chapter 2.6.1 “System data AC500” on page 971 are
applicable to the standard version.
The system data of AC500-XC
Ä
Chapter 2.7.1 “System data AC500-XC” on page 1023 are
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Process voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for +24 V
(UP) as well as 1.9, 2.9, 3.9 and 4.9 for 0 V
(ZP)
Rated value 24 V DC
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse on UP 10 A fast
Galvanic isolation Yes, per module
Current consumption
Device specifications