Technical data
The System Data of AC500-eCo apply 
Ä
 Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Galvanic isolation Yes, between the input groups and the rest of
the module
Isolated groups 2 (8 channels per group)
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Ca. 10 mA
Max. power dissipation within the module 6 W
Weight Ca. 222 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Technical data of the digital inputs
Parameter Value
Number of channels per module 16 AC inputs (100-240 V AC)
Distribution of the channels into groups 2 (8 channels per group)
Input voltage range 0 V AC...264 V AC (47 Hz...63 Hz)
Input current per channel (typically at 25 °C) < 3 mA (at 40 V AC)
> 6 mA (at 164 V AC)
> 8 mA (at 240 V AC)
Connections of the channels I0..I7 Terminals 1...8
Connections of the channels I8...I15 Terminals 10...17
Reference potential for the channels I0...I7 Terminal 9
Reference potential for the channels I8...I15 Terminal 18
Indication of the input signals 1 yellow LED per channel. The LED is on
when the input signal is high (signal 1).
Input type according to EN 61131-2 Type 1
Input signal range  
  Signal 0 (max.) 40 V AC
  Undefined signal 40 V AC < U < 79 V AC
  Signal 1 (min.) 79 V AC
Input delay  
  Signal 0 -> 1 Typ. 24 ms
  Signal 1 -> 0 Typ. 24 ms
Input data length 2 bytes
 
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US192