Loading...
Range -80 mV ... +80
mV
Type E
-270 ... +1000
°C
Types R, S
-50 ... +1768
°C
Digital value
Decimal Hex.
-80 mV -27648 9400
Underflow < -90 mV < -270.0 °C < -50.0 °C -32768 8000
Technical data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Process supply voltage UP
Connections Terminal 19 for UP (+24 V DC) and terminal 20
for ZP (0 V)
Rated value 24 V DC
Current consumption 0.10 A
Inrush current (at power-up) 0.07 A²s
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse for UP Not necessary
Current consumption from 24 V DC power
supply at the terminals UP/L+ and ZP/M of
the CPU/communication interface module
Ca. 5 mA
Galvanic isolation Yes, between the channels and the rest of the
module
Isolated groups 1 (4 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 2.6 W
Weight Ca. 120 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Device specifications