Fig. 84: Connection of analog output loads (current)
The following measuring ranges can be configured
Ä
Chapter 1.6.3.1.1.6 “Parameterization”
on page 565:
0
Current 0 mA...20 mA Load 0 W...500 W 1 channel used
Current 4 mA...20 mA Load 0 W...500 W 1 channel used
For a description of the function of the LEDs, please refer to the Diagnosis and displays /
Displays chapter
Ä
Chapter 1.6.3.1.1.8 “State LEDs” on page 572.
Unused analog outputs can be left open-circuited.
Internal data exchange
Without the fast counter With the fast counter (only
with AC500)
Digital inputs (bytes) 3 5
Digital outputs (bytes) 1 3
Analog inputs (words) 4 4
Digital outputs (words) 2 2
Counter input data (words) 0 4
Counter output data (words) 0 8
I/O configuration
The module does not store configuration data itself. It gets its parameterization data from the
master device of the I/O bus (CPU or communication interface module) during power-up of the
system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
I/O modules > Digital/Analog I/O modules
2022/01/313ADR010278, 3, en_US564