ABB AC500 V3 - Technical data of the fast counter

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Reference potential for AO0+ to AO1+ Terminal 1.7 (AO-) for voltage outputTerminal
1.9, 2.9 and 3.9 for current output
Output type
Unipolar Current
Bipolar Voltage
Galvanic isolation Against internal supply and other modules
Configurability -10...+10 V, 0...20 mA, 4...20 mA (each output
can be configured individually)
Output resistance (load), as current output 0...500 W
Output loadability, as voltage output ±10 mA max.
Indication of the output signals 1 LED per channel (brightness depends on the
value of the analog signal)
Resolution 12 bits (+ sign)
Settling time for full range change (resistive
load, output signal within specified tolerance)
Typ. 5 ms
Conversion error of the analog values
caused by non-linearity, adjustment error
at factory and resolution within the normal
range
Typ. 0.5 %, max. 1 %
Relationship between input signal and hex
code
Table Output ranges voltage and current
Ä
Chapter 1.7.4.1.9.3 “Output ranges voltage
and current” on page 763
Unused outputs Are configured as "unused" (default value) and
can be left open-circuited
Technical data of the fast counter
Parameter Value
Used inputs Terminal 2.0 (DI0), 2.1 (DI1)
Used outputs Terminal 3.0 (DO0)
Counting frequency Depending on operation mode:
Mode 1 - 6: max. 200 kHz
Mode 7: max. 50 kHz
Mode 9: max. 35 kHz
Mode 10: max. 20 kHz
Detailed description See
Device specifications
Communication interface modules (S500) > Modbus
2022/01/313ADR010278, 3, en_US768