Parameter Value
Output resistance (load),
as current output
0 W...500 W
Output loadability,
as voltage output
±10 mA max.
Indication of the output signals 1 LED per channel (brightness depends on
the value of the analog signal)
Resolution 12 bits (+ sign)
Settling time for full range change (resistive
load, output signal within specified tolerance)
Typ. 5 ms
Conversion error of the analog values caused
by non-linearity, adjustment error at factory
and resolution within the normal range
Typ. 0.5 %, max. 1 %
Relationship between input signal and hex
code
Ä
Chapter 1.6.3.1.2.9.3 “Output ranges
voltage and current” on page 608
Unused outputs Are configured as "unused" (default value)
and can be left open-circuited
Ordering data
Part no. Description Product life cycle phase *)
1SAP 250 800 R0001 DA502, digital/analog input/output
module, 16 DO, 8 DC, 4 AI, 2 AO
Active
1SAP 450 800 R0001 DA502-XC, digital/analog input/output
module, 16 DO, 8 DC, 4 AI, 2 AO,
XC version
Active
*) Modules in lifecycle Classic are available from stock but not recommended
for planning and commissioning of new installations.
Device specifications
I/O modules > Digital/Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 615