EasyManua.ls Logo

ABB AC500 V3 - Ordering data

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Value
Relay output voltage
Rated value 24 V DC or 120/240 V AC
Output delay
Switching 0 to 1 (max.) Typ. 10 ms
Switching 1 to 0 (max.) Typ. 10 ms
Output data length 2 bytes
Output current
Rated current per channel (max.) 2.0 A (24 V DC / 24 V AC / 48 V AC /
120 V AC / 240 V AC, only resistive loads)
2.0 A (24 V AC / 48 V AC / 120 V AC, only
pilot duty)
1.5 A (240 V AC, only pilot duty)
Rated current per group (max.) 10 A
Lamp load (max.) 200 W (230 V AC), 30 W (24 V DC)
Spark suppression with inductive AC loads Must be performed externally according to
driven load specification
Switching Frequencies
With resistive loads Max. 1 Hz
With inductive loads On Request
With lamp loads Max. 1 Hz
Output type Non-protected
Protection type
External fuse
1
)
Rated protection fuse 5 A fast
Short-circuit-proof / Overload-proof No, should be provided by an external fuse
or circuit breaker
Overload message No
Output current limitation No
Connection of 2 outputs in parallel Not possible
Lifetime of relay contacts (cycles) 100.000 at rated load
Max. cable length
Shielded 500 m
Unshielded 150 m
1
) Per group in case of group fuse protection. For each channel in case of channel-by-channel
fuse protection. The maximum current per group must not be exceeded.
Ordering data
Part no. Description Product life cycle phase *)
1SAP 231 300 R0000 DO573, digital output module, 16 DO,
relay output
Active
1TNE 968 901 R3101 Terminal block TA563-9, 9 pins, screw
front, cable side, 6 pieces per unit
Active
Device specifications
I/O modules > Digital I/O modules
2022/01/313ADR010278, 3, en_US242