Internal data exchange
Digital inputs (bytes) 0
Digital outputs (bytes) 0
Counter input data (words) 4
Counter output data (words) 4
I/O configuration
The module does not store configuration data itself. It gets its parameterization data from the
master device of the I/O bus (CPU or communication interface module) during power-up of the
system.
Hence, replacing I/O modules is possible without any re-parameterization via software.
Parameterization
Firmware version Configuration
Firmware version > V2.0.0 The arrangement of the parameter data is per-
formed by Control Builder Plus/ Automation
Builder software.
The parameter data directly influences the functionality of modules.
For non-standard applications, it is necessary to adapt the parameters to your system configura-
tion.
Module: Module slot address: Y = 1...10
No. Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
1 Module
ID
Internal 1505
1
)
Word 1505
0x05E1
0 65535 0x0Y01
2 Ignore
module
2
)
No
Yes
0
1
Byte No
0x00
Not for
FBP
3 Param-
eter
length in
bytes
Internal 21 Byte 21-CPU
21-FBP
0 255 0x0Y02
4 Check
supply
Off
On
0
1
Byte On
0x01
0 1 0x0Y03
5 Analog
data
format
Default 0 Byte Default
0x00
0x0Y04
6 Behav-
iour of
outputs
at com-
munica-
tion
errors
Off
Last
value
Substi-
tute
value
0
1+(n*5)
2+(n*5),
n £ 2
Byte Off
0x00
0 2 0x0Y05
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 511

Table of Contents