3
)
With "Module" the following allocation applies depending on the master:
Module error: I/O bus or PNIO: 31 = module itself; COM1/COM2: 1...10 =
expansion 1...10
Channel error: I/O bus or PNIO = module type (2 = DO); COM1/COM2:
1..10 = expansion 1..10
4
)
In case of module errors, with channel "31 = Module itself" is output.
State LEDs
LED State Color LED = OFF LED = ON
Outputs
O0...O7
Digital output Yellow Output is
OFF
Output is ON
(the output voltage is
only displayed if the
supply voltage of the
module is ON)
Technical data
The System Data of AC500-eCo apply
Ä
Chapter 2.5.1 “System data AC500-eCo V3”
on page 925
Only additional details are therefore documented below.
Parameter Value
Process supply voltage L+
Connections Terminal 20 for L+ (+24 V DC). The negative
pole is provided by the I/O bus.
Rated value 24 V DC
Current consumption via L+ 50 mA
Inrush current (at power-up) 0.0035 A²s
Max. ripple 5 %
Protection against reversed voltage Yes
Rated protection fuse for UP Recommended; the outputs must be pro-
tected by a 3 A fast-acting fuse
Current consumption from 24 V DC power
supply at the L+/UP and M/ZP terminals of the
CPU/communication interface module
Ca. 5 mA
Galvanic isolation Yes, between the output group and the rest
of the module
Isolated groups 2 (4 channels per group)
Surge-voltage (max.) 35 V DC for 0.5 s
Max. power dissipation within the module 2.0 W
Weight Ca. 150 g
Mounting position Horizontal or vertical
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.