ABB AC500 V3 - Resistance thermometer input ranges

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Range -20 ... +20
mA
0 ... +20 mA 4 ... 20 mA Digital value
Decimal Hex.
Measured
value too low
-0.0007
:
-3.5178
3.9994
:
1.1852
-1
:
-4864
FFFF
:
ED00
-20.0007
:
-23.5178
-27649
:
-32512
93FF
:
8100
Underflow < -23.5178 < -3.5178 < 1.1852 -32768 8000
Resistance thermometer input ranges
The represented resolution corresponds to 16 bits.
Range Pt100
-50 ...
+70 °C
1
)
Pt100 /
Pt1000
-50 ...
+400 °C
Pt100
-200 ...
+850 °C
Ni1000
-50 ...
+150 °C
Cu50
-200 ...
+200 °C
Digital value
Decimal Hex.
Overflow > 80.0 °C > 450.0
°C
> 850 °C > 160.0
°C
> 200 °C 32767 7FFF
Measured
value too
high
450.0 °C
:
400.1 °C
4500
:
4001
1194
:
0FA1
160.0 °C
:
150.1 °C
1600
:
1501
0640
:
05DD
80.0 °C
:
70.1 °C
800
:
701
0320
:
02BD
Normal
range
:
:
:
:
70.0 °C
:
0.1 °C
:
400.0 °C
:
:
:
:
0.1 °C
850.0 °C
:
:
:
:
:
0.1 °C
:
:
:
150.0 °C
:
:
0.1 °C
:
:
200.0 °C
:
:
:
0.1 °C
8500
4000
2000
1500
700
:
1
2134
0FA0
07D0
05DC
02BC
:
1
0.0 °C 0.0 °C 0.0 °C 0.0 °C 0 0000
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
:
-200 °C
-0.1 °C
:
-50.0 °C
-0.1 °C
:
-50.0 °C
2
)
-200.0 °C
2
)
-1
:
-500
-2000
FFFF
:
FE0C
F830