EasyManua.ls Logo

ABB AC500 V3 - Diagnosis

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 94: Channel monitoring
Internal
value
Monitoring
0 Plausibility, open-circuit (cut wire) and short circuit (default)
3 No monitoring
Table 95: Line frequency suppression
Internal
value
Line frequency suppression
0 50 Hz
1 60 Hz
2 No line frequency suppression
Table 96: Compensation channel
Internal
value
Compensation channel
0 Internal compensation (default)
1 Channel 0 (possible with channels 1, 2, 3)
2 Channel 1 (possible with channels 0, 2, 3)
3 Channel 2 (possible with channels 0, 1, 3)
4 Channel 3 (possible with channels 0, 1, 2)
5 Channel 4 (possible with channels 5, 6, 7)
6 Channel 5 (possible with channels 4, 6, 7)
7 Channel 6 (possible with channels 4, 5, 7)
8 Channel 7 (possible with channels 4, 5, 6)
9 External with temperature value
Diagnosis
E1...E4 d1 d2 d3 d4 Identifier
000...063
AC500
display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
browser
Byte 6
Bit 6...7
- Byte 3 Byte 4 Byte 5 Byte 6
Bit 0...5
FBP diag-
nosis
block
Class Interface Device Module Channel Error
identifier
Error message Remedy
1
)
2
)
3
)
4
)
Module error
3 14 1...10 31 31 19 Checksum error in the
I/O module
Replace
I/O module
11 / 12 ADR 1...10
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 475