EasyManua.ls Logo

ABB AC500 V3 - Page 538

ABB AC500 V3
1029 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
No. Name Value Internal
value
Internal
value,
type
Default Min. Max. EDS
Slot/
Index
33 Channel
moni-
toring
Output
channel
4
See
Ä
Table 112 “Chan
nel monitoring
3
)”
on page 539
Byte Default
0x00
0 3 0x0Y20
34
to
39
Channel
configu-
ration
and
channel
moni-
toring of
the
output
channels
5 to 7
See
Ä
Table 111 “Chan
nel configuration
2
)”
on page 538
and
Ä
Table 112 “Chan
nel monitoring
3
)”
on page 539
Byte
Byte
Default
0x00
0x00
0
0
128
3
0x0Y21
to
0x0Y26
1
) With CS31 and addresses less than 70 and FBP, the value is increased by 1
2
) Not with FBP
GSD file:
Ext_User_Prm_Data_Len =
Ext_User_Prm_Data_Const(0) =
24
0x05, 0xe2, 0x15, \
0x01, 0x00, 0x00 \
0x00, 0x00, 0x00, 0x00, 0x00, 0x00, 0x00,
0x00, \
0x00, 0x00, 0x00, 0x00, \
0x00, 0x00, 0x00, 0x00, 0x00, 0x00;
Table 110: Input channel (4x)
No. Name Internal value, type Default
1 Channel configuration
see table
2
)
Byte 0
0x00 see table
2
)
2 Channel monitoring
see table
3
)
Byte 0
0x00 see table
3
)
Table 111: Channel configuration
2
)
Internal value Operating modes of the analog inputs, individually configurable
0 Unused (default)
1 Analog input 0 V...10 V
2 Digital input
3 Analog input 0 mA...20 mA
Device specifications
I/O modules > Analog I/O modules
2022/01/313ADR010278, 3, en_US538

Table of Contents

Other manuals for ABB AC500 V3

Related product manuals