Parameter Value
With resistive loads Max. 1 Hz
With inductive loads On request
With lamp loads On request
Short-circuit-proof / Overload-proof No, should be provided by an external fuse
or circuit breaker
Rated protection fuse (for each channel) On request
Overload message No
Output current limitation No
Resistance to feedback against 24 V DC No
Connection of 2 outputs in parallel Not possible
Lifetime of relay contacts (cycles) 100,000 at rated load
Max. cable length *)
Shielded On request
Unshielded On request
*) For fast inputs and fast outputs including PTO and PWM, a shielded cable must be used and
the max. cable length is 50 m.
Table 18: PM5032-R-ETH and PM5052-R-ETH
Parameter Value
Number of channels per module 6 normally-open relay outputs
Distribution of the channels into groups 2 groups for 3 channels
Galvanic isolation Yes, per group
Connection of the channels NO0 to NO2 Terminals 14 to 16
Connection of the channels NO3 to NO5 Terminals 18 to 20
Reference potential R0..2 for the channels NO0
to NO2
Terminal 17
Reference potential R3..5 for the channels NO3
to NO5
Terminal 21
Relay output voltage
Rated value 24 V DC or
100 V AC...240 V AC
50 Hz/60 Hz
Range 5 V DC...30 V DC
or
5 V AC...250 V AC
Indication of the output signals 1 yellow LED per channel; the LED is on
when the output signal is high (signal 1) and
the module is powered through the I/O bus
Way of operation Non-latching type
Output delay
0 to 1 Typ. 10 ms
1 to 0 Typ. 10 ms
Rated protection fuse On request