After powering up the system, input channels, which are configured will have
undefined values /diagnosis message for typically 45 seconds, if the wires of all
configured channels are broken.
If the AI563 is connected to a PROFINET communication interface module, the
firmware version of PROFINET communication interface module must be 1.2 or
above.
The connection is carried out by using a removable 9-pin and 11-pin terminal block. These
terminal blocks differ in their connection system (spring terminals or screw terminals, cable
mounting from the front or from the side). The terminal blocks are not included in the module's
scope of delivery and must be ordered separately.
The following block diagram shows the internal construction of the analog inputs:
−−− 11
−−− 12
−−− 10
−−− 13
−−− 14
SG 16
SG 17
SG 15
UP 19
ZP 20
SG 18
I2 6
I3+ 7
I2+ 5
+
I3 8
−−− 9
I0 2
I1+ 3
I0+ 1
+
I1 4
+
+
The assignment of the terminals:
Terminal Signal Description
1 I0+ Positive pole of channel 0
2 I0- Negative pole of channel 0
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 373