Parameter Value
  Current consumption via UP (normal
operation)
0.2 A
  Current consumption via UP3 0.06 A + 0.5 A max. per output
  Connections Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Reference potential for all digital inputs and
outputs
Negative pole of the supply voltage, signal
name ZP
Setting of the CANopen Node ID identifier With 2 rotary switches at the front side of the
module
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
Required terminal unit TU509, TU510, TU517 or TU518
Ä
 Chapter 1.5.3 “TU517 and TU518 for com-
munication interface modules” on page 132
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
 
Communication interface modules (S500) > CANopen
2022/01/313ADR010278, 3, en_US622