5 6 74
Fig. 191: Connect the wire to the spring terminal (steps 4 to 7)
1. Side view (open terminal drawn for illustration)
2. The top view shows the openings for wire and screwdriver
3. Insert screwdriver (2.5 x 0.4 to 3.5 x 0.5 mm) at an angle, screwdriver must be at least 15
mm free of insulation at the tip
4. While erecting the screwdriver, insert it until the stop (requires a little strength)
5. Screwdriver inserted - terminal open
6. Strip the wire for 7 mm (and put on wire-end ferrule)
7. Insert wire into the open terminal
8. Done
2 3
Screwdriver
1
Screwdriver
Fig. 192: Disconnect wire from the spring terminal (steps 1 to 3)
Disconnection
System assembly, construction and connection
AC500 (Standard) > Connection and wiring
2022/01/31 3ADR010278, 3, en_US 993