The assignment of the terminals:
Terminal Signal Description
10 O0+ Current source of channel 0
11 I0+ Sense input of channel 0
12 I0- Return input of channel 0
13 O1+ Current source of channel 1
14 I1+ Sense input of channel 1
15 I1- Return input of channel 1
16 --- Reserved
17 SG Shield grounding
18 SG Shield grounding
19 UP Process voltage UP (24 V DC)
20 ZP Process voltage ZP (0 V DC)
The internal power supply voltage for the module's circuitry is carried out via the I/O bus
(provided by a communication interface module or a CPU). Thus, the current consumption from
24 V DC power supply at the terminals L+/UP and M/ZP of the CPU/communication interface
module increases by 5 mA per AI562.
The external power supply connection is carried out via the UP (+24 V DC) and the ZP (0 V DC)
terminals.
NOTICE!
Risk of imprecise and faulty measurements!
Analog signals may be distorted seriously by external electromagnetic influ-
ences.
Use shielded wires when wiring analog signal sources. The cable shield must
be grounded at both ends of the cable. Provide a potential equalisation of a
low resistance to avoid high potential differences between different parts of the
plant.
Device specifications
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 363