E1..E4 d1 d2 d3 d4 Identi-
fier
000..063
AC500-
Display
<− Display in
Class Comp Dev Mod Ch Err PS501
PLC
Browser
Byte 4
Bit 6..7
- Byte 1 Byte 2 Byte 3 Byte 4
Bit 0..5
CANope
n diag-
nosis
block
Class Inter-
face
Device Module Channel Error-
Identi-
fier
Error message Remedy
1
)
2
)
3
)
4
)
4 - 31 31 31 45 Process voltage
UP3 gone
Check
process
supply
voltage
4 - 31 31 31 10 Voltage overflow
on outputs (above
UP3 level)
5
)
Check
termi-
nals/
check
process
supply
voltage
Channel error digital
4 - 31 2 0...7 46 Voltage feedback
on deactivated dig-
ital output
6
)
Check
terminals
4 - 31 2 0...7 47 Short circuit at dig-
ital output
7
)
Check
terminals
Channel error analog
4 - 31 1 0..3 48 Analog value over-
flow or broken wire
at an analog input
Check
value or
check
terminals
4 - 31 1 0..3 7 Analog value
underflow at an
analog input
Check
value
4 - 31 1 0..3 47 Short circuit at an
analog input
Check
terminals
4 - 31 3 0..1 4 Analog value over-
flow at an analog
output
Check
output
value
4 - 31 3 0..1 7 Analog value
underflow at an
analog output
Check
output
value
Remarks:
Communication interface modules (S500) > CANopen
2022/01/31 3ADR010278, 3, en_US 647