NOTICE!
Risk of damaging the PLC modules!
Overvoltages and short circuits might damage the PLC modules.
Make sure that all voltage sources (supply voltage and process supply
voltage) are switched off before you begin with operations on the system.
Never connect any voltages or signals to reserved terminals (marked with
---). Reserved terminals may carry internal voltages.
The following figure shows the connection of the module:
1 I/O bus
2 Switchgear cabinet earth
NOTICE!
If the relay outputs have to switch inductive DC loads, free-wheeling diodes
must be circuited in parallel to these loads.
If the relay outputs have to switch inductive AC loads, spark suppressors
are required.
Device specifications
I/O modules > Digital I/O modules
2022/01/31 3ADR010278, 3, en_US 343