−−− 11
−−− 12
−−− 10
O0U+ 13
O0I+ 14
O1I+ 16
O01− 17
O1U+ 15
L+ 19
M 20
SG 18
+
+
−
−
The assignment of the terminals:
Terminal Signal Description
10 --- Reserved
11 --- Reserved
12 --- Reserved
13 O0U+ Voltage output of channel 0
14 O0I+ Current output of channel 0
15 O1U+ Voltage output of channel 1
16 O1I+ Current output of channel 1
17 O01- Negative pole of channels O0 and O1
18 SG Shield grounding
19 L+ Process voltage L+ (24 V DC)
20 M Process voltage M (0 V DC)
The internal power supply voltage for the module's circuitry is carried out via the I/O bus
(provided by a communication interface module or a CPU). Thus, the current consumption from
24 V DC power supply at the terminals UP/L+ and ZP/M of the CPU/communication interface
module increases by 5 mA per AO561.
The external power supply connection is carried out via the L+ (+24 V DC) and the M (0 V
DC) terminals. The M terminal is electrically interconnected to the M/ZP terminal of the CPU/
communication interface module.
NOTICE!
Risk of imprecise and faulty measurements!
Analog signals may be distorted seriously by external electromagnetic influ-
ences.
Use shielded wires when wiring analog signal sources. The cable shield must
be grounded at both ends of the cable. Provide a potential equalisation of a
low resistance to avoid high potential differences between different parts of the
plant.
I/O modules > Analog I/O modules
2022/01/31 3ADR010278, 3, en_US 385