The system data of AC500-XC
Ä
Chapter 2.7.1 “System data AC500-XC” on page 1023 are
applicable to the XC version.
Only additional details are therefore documented below.
The technical data are also applicable to the XC version.
Parameter Value
Process supply voltage
Connections Terminals 1.8, 2.8, 3.8 and 4.8 for UP (+24
V DC) and 1.9, 2.9, 3.9 and 4.9 for ZP (0 V
DC)
Protection against reverse voltage yes
Rated protection fuse at UP 10 A fast
Rated value 24 V DC
Max. ripple 5 %
Current consumption
From UP 0.07 A + max. 0.5 A per output
From 24 V DC power supply at the terminals
UP/L+ and ZP/M of the CPU/communication
interface module
ca. 2 mA
Inrush current from UP (at power-up)
0.04 A
2
s
Galvanic isolation Yes, per module
Max. power dissipation within the module 6 W (outputs unloaded)
Weight (without terminal unit) ca. 125 g
Mounting position Horizontal mounting or vertical with
derating (output load reduced to 50 % at
40 °C)
Cooling The natural convection cooling must not
be hindered by cable ducts or other parts
in the switchgear cabinet.
NOTICE!
Attention:
All I/O channels (digital and analog) are protected against reverse polarity,
reverse supply, short circuit and continuous overvoltage up to 30 V DC.
Multiple overloads
No effects of multiple overloads on isolated multi-channel modules occur, as
every channel is protected individually by an internal smart high-side switch.
I/O modules > Digital/Analog I/O modules
2022/01/313ADR010278, 3, en_US576