Parameter Value
Processor Hilscher NETX 100
Expandability CI58x can only be used on onboard CAN inter-
face and without any I/O expansion module
Ä
Table 132 “CANopen” on page 617.
State display Module state: PWR/RUN, CN-RUN, CN-ERR,
E-ERR, I/O bus
Adjusting elements 2 rotary switches for generation of the node
address
Ambient temperature
System data AC500
Ä
Chapter 2.6.1 “System
data AC500” on page 971
System data AC500 XC
Ä
Chapter 2.7.1
“System data AC500-XC” on page 1023
Current consumption UP: 0.2 A UP3: 0.06 A + 0.5 A max. per output
Weight (without terminal unit) Ca. 125 g
Process supply voltages UP/UP3
Rated value 24 V DC (for inputs and outputs)
Max. load for the terminals 10 A
Protection against reversed voltage Yes
Rated protection fuse on UP/UP3 10 A fast
Galvanic isolation CANopen interface against the rest of the
module
Inrush current from UP (at power up) On request
Current consumption via UP (normal
operation)
0.2 A
Current consumption via UP3 0.06 A + 0.5 A max. per output
Connections Terminals 2.8 and 3.8 for +24 V (UP)
Terminal 4.8 for +24 V (UP3)
Terminals 2.9, 3.9 and 4.9 for 0 V (ZP)
Max. power dissipation within the module 6 W
Reference potential for all digital inputs and
outputs
Negative pole of the supply voltage, signal
name ZP
Setting of the CANopen Node ID identifier With 2 rotary switches at the front side of the
module
Mounting position Horizontal
Or vertical with derating (output load reduced to
50 % at 40 °C per group)
Cooling The natural convection cooling must not be
hindered by cable ducts or other parts in the
switchgear cabinet.
Effect of incorrect input terminal connection Wrong or no signal detected, no damage up to
35 V
Required terminal unit TU509, TU510, TU517 or TU518
Ä
Chapter 1.5.3 “TU517 and TU518 for com-
munication interface modules” on page 132
Communication interface modules (S500) > CANopen
2022/01/313ADR010278, 3, en_US618